8 kW TO 50 kw

DOUBLE CONVERSION, FAST TRANSFER OR STAND BY SYSTEMS AVAILABLE TO POWER ALL LAMP TYPES INCLUDING LED and HID

LED, HID, Incandescent, Fluorescent

Installed in Office Buildings, Factories, Hospitals, Schools, Shopping Centers, Casinos, Airports, Train and Bus Terminals

WAVE RIDER 3

FEATURES

CSA Listed to UL924, UL924A, & UL1778
LED, Incandescent, Fluorescent, HID, HPS
Power Factor & Energy Efficient Ballast
92 - 98% Efficiency
Sinusoidal wave
Pulse width modulated (PWM)
Generator compatible
LCD Panel for Continuous Self Diagnostics
Modular Assembly for Ease of Installation
Battery exerciser
Double Conversion Technology or Fast Transfer
Seismic rated with bracket kit.
Stackable Cabinets
Remote Monitoring
RS 232 & RS 485
90 minutes runtime @ 100% load
Optional g-Battery, 20 years warranty
Global Monitoring System Option
2 year Factory Warranty

 

SPECIFICATIONS

Power Rating 8, 12, 16, 20, 24, 32, 40, and 50kW
Input Voltage 208Y/120 or 480Y/277 VAC (-20% to +15%)
Output Voltage 208Y/120 or 480Y/277 VAC
Output Frequency Inverter Operation: : 60Hz ±0.5Hz
Output Voltage Reg. ±3% Regulated within CBEMA curve
Output Waveform Sine-wave <5% THD
Efficiency 92 - 98% minimum
Crest Factor 3.1 Typical
Surge Protection The inverter will protect itself and the load against surge as defined in ANSI/IEEE C62.41 category A and B.
Isolation Complete from line. Output neutral bonded to ground
Noise Isolation -120 dB. Common-Mode.
60 dB. Transverse-Mode
Battery 10 Year pro rated maintenance free(AGM)Battery
Recharge Current Conforms to UL Standard
External Battery Provisions for hardware connection of optional external battery cabinets or DC source.
Environmental

Humidity: 0-95% RH w/no condensation

Operating Temperature:
UPS: 0°C to 40°C. (32°F to 104°F)
Battery: 20°C to 30°C. (68°F to 86°F)
Storage temperature: -20°C to 60°C. (-40°F to 140°F)

Safety Agencies CUL, CSA Listed UL1778, UL924, NFPA, NEC, OSHA.

 