UL924 ELEVATOR EMERGENCY BACKUP

Discover Crucial Power's innovative 24/7 monitored backup inverter system for Elevators. Revolutionizing emergency preparedness in response to the IBC & IFC naming Elevators as part of Emergency Evacuation/Life Safety Systems and requiring 2 Hours of emergency backup.  

WAVE RIDER ASCENT

FEATURES

ETL Certified to UL1778 and UL924
True Galvanic Isolation design
Designed to protect against a floating neutral
Advanced digital signal processing
Modular design for ease of troubleshooting and maintenance
Redundant multi-CPU design allows the software and hardware to work together as a team
The most intelligent and safe battery test circuitry available today
Individualized inverter support on each phase
Intelligent, fully temperature compensated battery charger
Hi-tech fan speed control
Optimum design for heat dissipation
Battery Power start feature
2 Year Limited Factory Warranty

 

SPECIFICATIONS

Power Rating 24, 32, 40, 50, 64, 80, 96, 128, 160, 192 and 240kW
Input Voltage 208Y/120 or 480Y/277 VAC (-15% to +15%)
Output Voltage 208Y/120 or 480Y/277 VAC
Output Frequency 60Hz ±1Hz (Inverter Operation)
Output Voltage Reg. ±1% at 100% unbalanced load
Output Waveform Sine-wave <2% THD
Crest Factor 3.1 Typical
Surge Protection The UPS will protect itself and the load against surge as defined in ANSI/IEEE C62.41 category A and B.
Isolation True galvanic isolated
Battery Sealed maintenance-free VRLA or Long Life Battery (available upon request)
Recharge Time Varies per KVA and conforms to UL924
Environmental

Humidity: 0-95% RH w/no condensation
Operating Temperature:
UPS: 0°C to 40°C. (32°F to 104°F)
Battery: 20°C to 30°C. (68°F to 86°F)
Storage temperature: -20°C to 60°C. (-40°F to 140°F)

Safety Agencies ETL Certified to UL1778 and UL924, NFPA, NEC, OSHA.

 

Download
Documents

PDF format
Word Format