On-Line Inverter(uninterruptible)


FEATURES

2.1 to 17 kW, Single Phase
UL924 Listed
Manufactured for Hostile
Environments
Outdoor Applications
Remote Locations
Incandescent, Fluorescent, or HID


INPUT SPECIFICATION

Nominal Input Voltage: 120, or 208, or 240, 277 or 480 VAC single phase
Input Voltage Range: +20% to -35%
Input Frequency: 60 Hz +5%
Power Factor: Unity 1.0
Overcurrent Protection: Circuit breaker
Power Connection: Hard wired (terminal block)
Input Configuration: 2 wire (hot, neutral) plus ground

OUTPUT SPECIFICATION

Output Rating:
2.1, 3.5, 5.25, 7, 8.75, 10.5, 15 and 17 kW
(Normal Mode/Emergency Mode)
Voltage: 120/240, 277, 480 VAC, Single Phase
Voltage Regulation: +3% No Load to Full Load;
+3% High Line to Low Line
Frequency: 60 Hz +0.25 Hz (When on Inverter)
Waveshape: Sine Wave
Harmonic Distortion: <7% THD; <5% Single Harmonic
Crest Factor: Up to 3 to 1
Power Factor
: unity to 15 kW
Overload: 125% for Ten (10) Minutes; 150% Surge
Noise Rejection: -120 dB Common Mode; -60 dB Normal Mode
Operating Temp: Tested for -29F(-34C) to 136F(58C)

PHYSICAL SPECIFICATION

Accessibility: All Servicing is through the Front.
Cable Entry: Bottom
Mounting: Four (4) Mounting Holes Provided to Anchor
Enclosure to Pedestal

BATTERY SPECIFICATION

Battery Run Time: 90 min
Battery Type: Sealed, Maintenance-Free, Lead calcium
Nominal DC Link: 48 or 120 VDC link
Overcurrent Protection: Circuit Breaker




Watts
Model Numbers
INPUT VOLTAGE
OUTPUT VOLTAGE
BTUs
/Hour
NO. OF CABINETS AND DIMENSIONS (W x D x H)
WEIGHT (LBS)
*Inv Only
2100
HU3.0A01TLF1-96
120, 208, 240, 277
120, 208, 240, 277
1137
(1) 39 x 20 x 74.5
910
3000
HU3.0A01TLF2-96
120, 208, 240, 277
120, 208, 240, 277
1433
(1) 39 x 20 x 74.5
910
3500
HU5.0A01TLF1-96
120, 208, 240, 277
120, 208, 240, 277
1314
(1) 39 x 20 x 74.5
985
5000
HU5.0A01TLF2-96
208, 240, 277
120, 208, 240, 277
2047
(1) 39 x 20 x 74.5
985
5250
HU7.5A01TLF1-96
208, 240, 277
120, 208, 240, 277
2150
(1) 39 x 20 x 74.5
1070
7000
HU010A01TLF1-96
208, 240, 277
120, 208, 240, 277
1085
(2) 39 x 20 x 74.5
1085
7500
HU7.5A01TLF2-96
208, 240, 277
120, 208, 240, 277
3070
(2) 39 x 20 x 74.5
1070
8750
HU12.5A01TLF1-96
208, 240, 277
120, 208, 240, 277
3070
(2) 39 x 20 x 74.5
1130
10000
HU010A01TLF2-96
208, 240, 277
120, 208, 240, 277
4094
(2) 39 x 20 x 74.5
1085
10500
HU015A01TLF1-96
208, 240, 277
120, 208, 240, 277
4299
(2) 39 x 20 x 74.5
1285
12500
HU12.5A01TLF2-96
208, 240, 277
120, 208, 240, 277
5118
(2) 39 x 20 x 74.5
3517
14000
HU020A01TLF1-96
208, 240, 277
120, 208, 240, 277
5732
(2) 39 x 20 x 74.5
1285
15000
HU015A01TLF2-96
208, 240, 277
120, 208, 240, 277
6141
(3) 39 x 20 x 74.5
1285
17000
HU017A01TLF2-96
208, 240, 277
120, 208, 240, 277
6141
(3) 39 x 20 x 74.5
1285

* Ask factory for battery cap. weights