On-Line Inverter(uninterruptible)
|
FEATURES
 |
2.1 to 17 kW, Single Phase
|
 |
UL924 Listed
|
 |
Manufactured for Hostile |
 |
Environments
|
 |
Outdoor Applications
|
 |
Remote Locations
|
 |
Incandescent, Fluorescent, or HID
|
|
|
|
|
|
 |
|
INPUT SPECIFICATION
Nominal Input Voltage: 120, or 208, or 240,
277 or 480 VAC single phase
Input Voltage Range: +20% to -35%
Input Frequency: 60 Hz +5%
Power Factor: Unity 1.0
Overcurrent Protection: Circuit breaker
Power Connection: Hard wired (terminal block)
Input Configuration: 2 wire (hot, neutral) plus ground
|
|
OUTPUT SPECIFICATION
Output Rating: 2.1, 3.5, 5.25, 7, 8.75, 10.5, 15 and 17
kW
(Normal Mode/Emergency Mode)
Voltage: 120/240, 277,
480 VAC, Single Phase
Voltage Regulation: +3% No Load to Full Load;
+3% High Line to Low Line
Frequency: 60 Hz +0.25 Hz (When on Inverter)
Waveshape: Sine Wave
Harmonic Distortion: <7% THD; <5% Single Harmonic
Crest Factor: Up to 3 to 1
Power Factor: unity to 15 kW
Overload: 125% for Ten (10) Minutes; 150% Surge
Noise Rejection: -120 dB Common Mode; -60 dB Normal Mode
Operating Temp: Tested for -29F(-34C) to 136F(58C)
|
PHYSICAL SPECIFICATION
Accessibility: All Servicing is through the Front.
Cable Entry: Bottom
Mounting: Four (4) Mounting Holes Provided to Anchor
Enclosure to Pedestal
|
BATTERY SPECIFICATION
Battery Run Time: 90 min
Battery Type: Sealed, Maintenance-Free, Lead calcium
Nominal DC Link: 48 or 120 VDC link
Overcurrent Protection: Circuit Breaker
|


|
|
Watts
|
Model Numbers
|
INPUT VOLTAGE
|
OUTPUT VOLTAGE
|
BTUs /Hour
|
NO. OF CABINETS AND DIMENSIONS (W x D x H)
|
WEIGHT (LBS)
*Inv Only
|
|
2100
|
HU3.0A01TLF1-96
|
120, 208, 240, 277
|
120, 208, 240, 277
|
1137
|
(1) 39 x 20 x 74.5
|
910
|
|
3000 |
HU3.0A01TLF2-96
|
120, 208, 240, 277
|
120, 208, 240, 277
|
1433
|
(1) 39 x 20 x 74.5
|
910
|
|
3500
|
HU5.0A01TLF1-96
|
120, 208, 240, 277
|
120, 208, 240, 277
|
1314
|
(1) 39 x 20 x 74.5
|
985
|
|
5000 |
HU5.0A01TLF2-96
|
208, 240, 277
|
120, 208, 240, 277
|
2047
|
(1) 39 x 20 x 74.5
|
985
|
|
5250
|
HU7.5A01TLF1-96
|
208, 240, 277
|
120, 208, 240, 277
|
2150
|
(1) 39 x 20 x 74.5
|
1070
|
|
7000
|
HU010A01TLF1-96
|
208, 240, 277
|
120, 208, 240, 277
|
1085
|
(2) 39 x 20 x 74.5
|
1085
|
|
7500
|
HU7.5A01TLF2-96
|
208, 240, 277
|
120, 208, 240, 277
|
3070
|
(2) 39 x 20 x 74.5
|
1070
|
|
8750
|
HU12.5A01TLF1-96
|
208, 240, 277
|
120, 208, 240, 277
|
3070
|
(2) 39 x 20 x 74.5
|
1130
|
|
10000
|
HU010A01TLF2-96
|
208, 240, 277
|
120, 208, 240, 277
|
4094
|
(2) 39 x 20 x 74.5
|
1085
|
|
10500
|
HU015A01TLF1-96
|
208, 240, 277
|
120, 208, 240, 277
|
4299
|
(2) 39 x 20 x 74.5
|
1285
|
|
12500
|
HU12.5A01TLF2-96
|
208, 240, 277
|
120, 208, 240,
277
|
5118
|
(2) 39 x 20 x 74.5
|
3517
|
|
14000 |
HU020A01TLF1-96
|
208, 240, 277
|
120, 208, 240, 277
|
5732
|
(2) 39 x 20 x 74.5
|
1285
|
|
15000
|
HU015A01TLF2-96
|
208, 240, 277
|
120, 208, 240, 277
|
6141
|
(3) 39 x 20 x 74.5
|
1285
|
|
17000
|
HU017A01TLF2-96
|
208, 240, 277
|
120, 208, 240, 277
|
6141
|
(3) 39 x 20 x 74.5
|
1285
|
|
* Ask factory for battery cap.
weights

|
|
|